Vibration checks detected high-frequency peaks indicating an outer race bearing fault in the cooler fan motor. Early detection allows for planned corrective action.
Early Signs of Bearing wear – Cooler Fan Motor
Routine vibration checks revealed increasing high-frequency peaks. The latest spectrum showed clear alignment with the BPFO, pointing to an outer race bearing fault.
Thanks to trending and early detection, we can now plan corrective action and avoid unexpected downtime. Predictive maintenance doing what it does best!